Hei alle sammen, eg har et oppsett for å lese ut en del verdier via modbus på mitt Villavent / Systemair VTR150. Det er tilkoblet via en modbus-til-ethernet converter. I min konfigurasjon har eg følgende innlesing: modbus: - name: vtr150 type: tcp host: 10.160.1.98 port: 8234 timeout: 3 delay: 5 close_comm_on_error: false retry_on_empty: true retries: 10 sensors: - name: Utetemperatur unit_of_measurement: °C scale: 0.1 precision: 1 scan_interval: 10 slave: 1 address: 12101 data_type: int device_class: temperature - name: Tilførselsluft unit_of_measurement: °C scale: 0.1 precision: 1 scan_interval: 10 slave: 1 address: 12102 data_type: int device_class: temperature - name: Utluft unit_of_measurement: °C precision: 1 scan_interval: 10 slave: 1 address: 12543 data_type: int device_class: temperature - name: Luftfuktighet unit_of_measurement: "%" scale: 1 precision: 1 scan_interval: 10 slave: 1 address: 12135 data_type: int device_class: humidity - name: RH-sensor unit_of_measurement: "%" scale: 1 precision: 1 scan_interval: 10 slave: 1 address: 1000 data_type: int device_class: humidity - name: Viftemodus slave: 1 address: 1130 precision: 0 count: 1 data_type: uint Mitt problem er at verdien "Utluft" blir vist som 210 grader C når den skulle vere 21 grader C. Altså en type konverteringsfeil. Korleis kan eg få endra dette i konfigurasjonen eller før dataene sendes til via Homebridge til IOS?